Product Code: CHINAELABC4470009
Categories: Oil Insulation Testers
Secondary and Relay Testing Kits 100 AMPS
Secondary /Relay Testing Kits - 100 AMPS
Secondary /Relay Testing Kits - 100 AMPS
Secondary /Relay Testing Kits - 100 AMPS
Secondary /Relay Testing Kits - 200 AMPS
Secondary /Relay Testing Kits - 50 AMPS
Input : 240V ±10%, AC, 50/60Hz.
Digital Timer : 4 digit, solid state, time interval measuring system, 5 ranges from .0001 to 9999 seconds.
Accuracy : ±0.5% + 1 count.
Timer Control Circuits : Timer automatically starts when output is initiated and automatically stops when the device. under test operates.
Test Conditions : Normally open contacts (Potential free) / Normally closed contacts (Potential Free).
Auto cut-off : Cuts off output on operation of device under test.
Duty cycle : 10 mins ON / 15 mins OFF.
Metering : Digital LED volt and amp meters. Accuracy: ± 1% ± 3 digits.
Operation : A SET / TEST switch is provided so that the appropriate test current can be set up before the test is actually
carried out, and to avoid damage to relay coils by disconnecting the test current after the relay has operated.
Construction : Sheet metal cabinet powder coated with cover and lifting handles.
Accessories : 3 core mains cord, Test leads-2 metre long and operating manual.
Technical Specification
Output : Two independently adjustable outputs available simultaneously
AC Current :
100A at 0-5V AC
50A at 0-10V AC
25A at 0-20V AC
10A at 0-50V AC
2.5A at 0-75V AC
1A at 0-150V AC
Each of these outputs has a separate terminal referred to one common terminal.
Duty Cycle : 15 min ON/15 min OFF
Voltage : 0-230V, 1A, DC full wave unsmoothed
0-230V, 1A, AC fully isolated
Each of these outputs has a separate pair of terminals.
Metering : Current/Voltage: Digital 12.5mm LED meters Current Displays output in Amperes 0-2-20-100A, Voltage Separate meters for AC and DC outputs 300V.